Steam Flow Computer
The 515-SC01 steam flow computer measures the volume, mass and energy content of steam by using frequency volume flow input in conjunction with analog temperature and/or pressure input.
A selection of various modes makes it suitable for many steam applications. The instrument is compatible with a wide range of flowmeter frequency outputs. Millivolt signals, reed switches, Namur proximity switches or pulse trains can be selected via its smart front-panel programming.
The flow computer calculates the mass flow and energy according to the IAPWS Industrial Formulation (1997) for the thermodynamic properties of steam. The equations use the pressure and temperature values to determine the specific volume and the specific enthalpy.
Calculations
The steam energy calculations are based on the IAPWS Industrial Formulation (1997).
Superheated steam regions are:
• 0°C < t < 800°C P < 100MPa
• 32°F < t < 1472°F P < 14500psia
• 800°C < t < 2000°C P < 10MPa
• 1472°F < t < 3632°F P < 1450psia
Saturated steam regions are:
• 0°C < t < 374°C (critical temperature)
• 32°F < t < 705°F
• P < 22MPa (critical pressure)
• P < 3190psia
Water region is:
• 0°C < t < t saturation at system pressure
• 32°C < t < t saturation at system pressure
Formulas:
• Mass flow = Volume flow/Specific volume
• Energy flow = Mass flow x Specific enthalpy
Features
Uses IAPWS-IF97 steam calculation
Suitable for Water, Saturated and Superheated steam applications
Allows for non-linear correction
Selection of second language and user tags
RTC logging with over 1000 entries
Infra-red communications port on front panel
Pulse width and scaling of pulse output
4-20mA retransmission
Selectable protocols on serial ports including Modbus RTU and printer output
Front panel adjustment of 8-24V DC output voltage
Backlit display
LCD backup Typical plant diagram
Downloads
Related Accessories
Software – Program Manager (Download)
Software – DataMod Tool
IP65 – Stainless Steel (Custom)
IP66 – Weatherproof Enclosure
PR-00 – Thermal Panel Printer
PR-01 – Roll Printer (Panel Mount Impact)
PR-02 – Desktop 24VDC or 240VAC
PR-03 – Desktop 240VAC 80 Col
PR-04 – Thermal Ticket Printer