The 515 BF01 application is a batching controller for delivery of preset quantities at preset flowrates using a volumetric frequency input. Batch control can operate in preset or on-off modes, while flow control can be set to local (manual) or PI loop mode.
This application provides the operator with clear local readout including flowrate deviation and can be controlled via communications in more automated systems. There is quick access to commonly used preset values directly from the front panel if access has been authorized.
The PI control of the process flow is via a 4-20mA proportional valve or pump controller. It has integral wind- up protection, a deadband, output hold and ramp time that can be programmed to reduce wear on valves and actuators and provide for bumpless operation.
The total and flowrate are derived from accurately measured frequency and the number of received pulses.
volume = pulses / k-factor
volume flow = frequency / k-factor
Automatic overrun compensation calculates the new valve closure point to ensure correct delivery by averageing the overrun amount from the last three complete batches.
The overrun compensation value is valid for a new preset value provided the stored overrun is less than 20% of the new preset.

The front panel display shows the current values of the input variables and the results of the calculations. A list of the variables for this application and their type (total or rate) is shown at the end of this document.
The instrument can be supplied with a real-time clock for storage of up to 100 transactions with time and date stamps.
There are three communication ports available as follows:
The ports are available for remote data reading, printouts and for initial application loading of the instrument.
The opto-isolated outputs can retransmit any main menu variable. The type of output is determined by the nature of the assigned variable. Totals are output as pulses and rates are output as 4-20 mA signals. One output is standard, a second output is available as an option.
The relay outputs 1 and 2 are used to control the flow of product for each delivery. These contacts are normally open and can be used to drive external relays, valves, pump circuits etc.
The instrument can be further tailored to suit specific application needs including units of measurement, custom tags, second language or access levels. A distributor can configure these requirements before delivery.
Instrument parameters including units of measurement can be programmed in the field, according to the user access levels assigned to parameters by the distributor.
All set-up parameters, totals and logged data are stored in non-volatile memory with at least 30 years retention.

| Terminal Label | Designation | Comment | ||
|---|---|---|---|---|
| 1 | FINP | 1+ | Frequency Input 1+ | Volumetric flow Input |
| 3 | SG | - | Signal Ground | |
| 15 | Vo | + | 8-24 volts DC output | Overload protected |
| 16 | G | - | DC Ground | |
| 17 | Vi | + | DC power input | DC power in 12-28V |
| 18 | SH | E | Shield terminal | |
| 19 | RS485 | + | RS485 (+) | Advanced option |
| 20 | RS485 | - | RS485 (-) | Advanced option |
| 21 | RS485 | G | RS485 Ground | Advanced option |
| 22 | LOGIC INPUTS | 1+ | Switch 1 | Remote Run |
| 23 | LOGIC INPUTS | 2+ | Switch 2 | Remote Stop |
| 24 | LOGIC INPUTS | 3+ | Switch 3 | Remote Reset |
| 25 | LOGIC INPUTS | 4+ | Switch 4 | Permissive Input |
| 26 | LOGIC INPUTS | C- | Signal ground | |
| 27 | OUT 1 | + | Output ch 1 (+) | Process control output |
| 28 | OUT 1 | - | Output ch 1 (-) | Process control output |
| 29 | OUT 2 | + | Output ch 2 (+) | Optional Output |
| 30 | OUT 2 | - | Output ch 2 (-) | Optional Ouput |
| 31 | RELAYS | RC | Relay common | |
| 32 | RELAYS | R1 | Relay 1 | Single stage control |
| 33 | RELAYS | R2 | Relay 2 | Dual stage control |
| 34 | RELAYS | R3 | Relay 3 | Advanced option |
| 35 | RELAYS | R4 | Relay 4 | Advanced option |
| E | AC MAINS | E | Mains ground | AC power in 95-135V or 190-260V |
| N | AC MAINS | N | Mains neutral | AC power in 95-135V or 190-260V |
| A | AC MAINS | A | Mains active | AC power in 95-135V or 190-260V |
| RS232 port | 9-pin serial port |
515.XXXXXX-BF01
See product codes to select required features
Default application software:
515-BF01-000000

Operating Environment
-20 °C to +60 °C (conformal coating)
+5 °C to +40 °C (no coating)
0 to 95% non condensing (conformal coating)
5% to 85% non condensing (no coating)
95…135 V AC or 190…260 V AC or
12…28 V DC
6W (typical)
Sealed to IP65 (Nema 4X) when panel mounted
147 mm (5.8″) width
74 mm (2.9″) height
167 mm (6.6″) depth
Display
Backlit LCD with 7-digit numeric display and 11-character alphanumeric display
15.5 mm (0.6″) high
6 mm (0.24″) high
Last data visible for 15 min after power down
0.3 second
Non-volatile Memory
> 30 years
Setup, Totals and Logs
Approvals
CE compliance
ATEX, FM, CSA and SAA approved enclosures available for hazardous areas
Real Time Clock (Optional)
3 volts Lithium button cell (CR2032)
5 years (typical)
Frequency Input (General)
0 to 10 kHz
30 V maximum
0.3 sec
Programmable
Pulse, coil or NPS input
Up to 10 correction points
Pulse
CMOS, TTL, open collector, reed switch
1.3 volts
Coil
Turbine and sine wave
15 mV p-p minimum
NPS
NPS sensor to Namur standard
Logic Inputs
CMOS, TTL, open collector, reed switch
30V maximum
Relay Output
2 relays plus 2 optional relays
250 volts AC, 30 volts DC maximum (solid state relays use AC only)
3 A maximum
Communication Ports
RS-232 port
RS-485 port (optional)
Infra-red port
2400 to 19200 baud
Odd, even or none
1 or 2
ASCII, Modbus RTU, Printer
Transducer Supply
8 to 24 volts DC, programmable
70 mA @ 24 V, 120 mA @ 12 V maximum
Power limited output
Isolated Output
1 configurable output (plus 1 optional)
Pulse/Digital or 4-20 mA output
Pulse/Digital Output
Open collector
200 mA, 30 volts DC maximum
0.8 volts maximum
Programmable: 10 , 20, 50, 100, 200 or 500ms
4-20mA Output (Optional)
9 to 30 volts DC external
0.05% full scale
0.05% full scale (20°C)
0.1% (full temperature range, typical)
Important: Specifications are subject to change without notice.
| Model | Supplementary Code | Description | ||||||
|---|---|---|---|---|---|---|---|---|
| 515 | - | BF01 | ||||||
| Enclosure | 1 | Panel mount enclosure | ||||||
| Enclosure | 2 | Field mount enclosure (not yet available) | ||||||
| Enclosure | 3/5 | Explosion proof Ex410 with metric glands (5 specifies heater version) | ||||||
| Enclosure | 4/6 | Explosion proof Ex410 with NPT glands (6 specifies heater version) | ||||||
| Output Options | 0 | 4 logic inputs, 1 isolated output, 2 relays (only relay type 1 is available), RS232 (DB9) communication port | ||||||
| Output Options | 1 | 4 logic inputs, 2 isolated outputs, 4 relays, real-time clock data logging, RS232 (DB9) and RS485 communication ports | ||||||
| Output Options | 2/3 | 4 logic inputs, 2 isolated outputs, 4 relays, real-time clock data logging, RS232 (DB9) and Ethernet/RF communication ports (not yet available) | ||||||
| Relay Type | 1 | Electromechanical relays only | ||||||
| Relay Type | 2 | 2 electromechanical and 2 solid state relays | ||||||
| Relay Type | 3 | Solid state relays only (not yet available) | ||||||
| Power Supply | E | For 220/240 VAC | ||||||
| Power Supply | A | For 110/120 VAC | ||||||
| Power Supply | D | For DC power only 12-28 VDC | ||||||
| Display Panel Options | F | Fully optioned (with backlight, LCD backup and Infra-Red comms port) | ||||||
| PCB Protection | C | Conformal coating - required for maximum environmental operating range. Recommended to avoid damage from moisture and corrosion. | ||||||
| PCB Protection | N | None - suitable for IEC standard 654-1 Climatic Conditions up to Class B2 (Heated and/or cooled enclosed locations) | ||||||
| Application Pack Number | BF01 | Defines the application software to be loaded into the instrument | ||||||
| Main Menu Variables | Default Units | Preferred Units | Variable Type |
|---|---|---|---|
| Volume | Ltr | Total | |
| Volume Flowrate | L/min | Rate | |
| Control Output | % | - - - | Rate |
| Flowrate Deviation | % | Rate |
Please specify the preferred units of measurement.

The 515 BF02 application is a batching flow controller for delivery of preset quantities at preset flowrates using a volumetric analog input. Batch control can operate in preset or on-off modes, while flow control can be set to local manual) or PI loop mode.
This application provides the operator with clear local readout including flowrate deviation and can be controlled via communications in more automated systems. There is quick access to commonly used preset values directly from the front panel if access has been authorized.
The PI control of the process flow is via a 4-20mA proportional valve or pump controller. It has integral wind- up protection, a deadband, output hold and ramp time that can be programmed to reduce wear on valves and actuators and provide for bumpless operation.
To derive the flow rate, the analog input is normalised to a value (A) between 0 and 1.
mass flow = (Mf max – Mf min)A + Mf min mass = ∫( massflow × Δt )
Automatic overrun compensation calculates the new valve closure point to ensure correct delivery by averageing the overrun amount from the last three complete batches.
The overrun compensation value is valid for a new preset value provided the stored overrun is less than 20% of the new preset.

The front panel display shows the current values of the input variables and the results of the calculations. A list of the variables for this application and their type (total or rate) is shown at the end of this document.
The instrument can be supplied with a real-time clock for storage of up to 100 transactions with time and date stamps.
There are three communication ports available as follows:
The ports are available for remote data reading, printouts and for initial application loading of the instrument.
The opto-isolated outputs can retransmit any main menu variable. The type of output is determined by the nature of the assigned variable. Totals are output as pulses and rates are output as 4-20 mA signals. One output is standard, a second output is available as an option.
The relay outputs 1 and 2 are used to control the flow of product for each delivery. These contacts are normally open and can be used to drive external relays, valves, pump circuits etc.
The instrument can be further tailored to suit specific application needs including units of measurement, custom tags, second language or access levels. A distributor can configure these requirements before delivery.
Instrument parameters including units of measurement can be programmed in the field, according to the user access levels assigned to parameters by the distributor.
All set-up parameters, totals and logged data are stored in non-volatile memory with at least 30 years retention.

| Terminal Label | Designation | Comment | ||
|---|---|---|---|---|
| 3 | SG | - | Signal ground | |
| 11 | AINP3 | + | Analog input ch 3 (+) | Main or low flow input |
| 12 | AINP3 | - | Analog input ch 3 (-) | Main or low flow input |
| 13 | AINP4 | + | Analog input ch 4 (+) | High flow stacked input |
| 14 | AINP4 | - | Analog input ch 4 (-) | High flow stacked input |
| 15 | Vo | + | 8-24 volts DC output | Overload protected |
| 16 | G | - | DC Ground | |
| 17 | Vi | + | DC power input | DC power in 12-28V |
| 18 | SH | E | Shield Terminal | |
| 19 | RS485 | + | RS485(+) | Advanced option |
| 20 | RS485 | - | RS485(+) | Advanced option |
| 21 | RS485 | G | RS485 ground | Advanced option |
| 22 | Logic Inputs | 1+ | Switch 1 | Remote Run |
| 23 | Logic Inputs | 2+ | Switch 2 | Remote Stop |
| 24 | Logic Inputs | 3+ | Switch 3 | Remote reset |
| 25 | Logic Inputs | 4+ | Switch 4 | Permissive Input |
| 26 | Logic Inputs | C- | Signal ground | |
| 27 | Out 1 | + | Output ch 1 (+) | Process control output |
| 28 | Out 1 | - | Output ch 1 (-) | Process control output |
| 29 | Out 2 | + | Output ch 2 (+) | Advanced Option |
| 30 | Out 2 | - | Output ch 2 (-) | Advanced Option |
| 31 | RELAYS | RC | Relay Common | |
| 32 | RELAYS | R1 | Relay 1 | Single Stage Control |
| 33 | RELAYS | R2 | Relay 2 | Dual Stage Control |
| 34 | RELAYS | R3 | Relay 3 | Advanced Option |
| 35 | RELAYS | R4 | Relay 4 | Advanced Option |
| E | AC MAINS | E | Mains ground | AC power in 95-135 V or 190-260 V |
| N | AC MAINS | N | Mains neutral | AC power in 95-135 V or 190-260 V |
| A | AC MAINS | A | Mains active | AC power in 95-135 V or 190-260 V |
| RS232 port | 9-pin serial port | |||
515.XXXXXX-BF02
See product codes to select required features
Default application software:
515-BF02-000000

Operating Environment
-20 °C to +60 °C (conformal coating)
+5 °C to +40 °C (no coating)
0 to 95% non condensing (conformal coating)
5% to 85% non condensing (no coating)
95…135 V AC or 190…260 V AC or
12…28 V DC
6W (typical)
Sealed to IP65 (Nema 4X) when panel mounted
147 mm (5.8″) width
74 mm (2.9″) height
167 mm (6.6″) depth
Display
Backlit LCD with 7-digit numeric display and 11-character alphanumeric display
15.5 mm (0.6″) high
6 mm (0.24″) high
Last data visible for 15 min after power down
0.3 second
Non-volatile Memory
> 30 years
Setup, Totals and Logs
Approvals
CE compliance
ATEX, FM, CSA and SAA approved enclosures available for hazardous areas
Real Time Clock (Optional)
3 volts Lithium button cell (CR2032)
5 years (typical)
Analog Input (General)
100 mA absolute maximum rating
< 1.0 sec
4-20 mA, 0-5V and 1-5V input
Up to 20 correction points (flow inputs)
4-20 mA Input
100 ohms (to common signal ground)
0.05% full scale (20 °C)
0.1% (full temperature range, typical)
0-5 or 1-5 Volts Input
10 Mohms (to common signal ground)
0.05% full scale (20 °C)
0.1% (full temperature range, typical)
Logic Inputs
CMOS, TTL, open collector, reed switch
30V maximum
Relay Output
2 relays plus 2 optional relays
250 volts AC, 30 volts DC maximum (solid state relays use AC only)
3 A maximum
Communication Ports
RS-232 port
RS-485 port (optional)
Infra-red port
2400 to 19200 baud
Odd, even or none
1 or 2
ASCII, Modbus RTU, Printer
Transducer Supply
8 to 24 volts DC, programmable
70 mA @ 24 V, 120 mA @ 12 V maximum
Power limited output
Isolated Output
1 configurable output (plus 1 optional)
Pulse/Digital or 4-20 mA output
Pulse/Digital Output
Open collector
200 mA, 30 volts DC maximum
0.8 volts maximum
Programmable: 10 , 20, 50, 100, 200 or 500ms
4-20mA Output (Optional)
9 to 30 volts DC external
0.05% full scale
0.05% full scale (20°C)
0.1% (full temperature range, typical)
Important: Specifications are subject to change without notice.
| Model | Supplementary Code | Description | ||||||
|---|---|---|---|---|---|---|---|---|
| 515 | - | BF02 | ||||||
| Enclosure | 1 | Panel mount enclosure | ||||||
| Enclosure | 2 | Field mount enclosure (not yet available) | ||||||
| Enclosure | 3/5 | Explosion proof Ex410 with metric glands (5 specifies heater version) | ||||||
| Enclosure | 4/6 | Explosion proof Ex410 with NPT glands (6 specifies heater version) | ||||||
| Output Options | 0 | 4 logic inputs, 1 isolated output, 2 relays (only relay type 1 is available), RS232 (DB9) communication port | ||||||
| Output Options | 1 | 4 logic inputs, 2 isolated outputs, 4 relays, real-time clock data logging, RS232 (DB9) and RS485 communication ports | ||||||
| Output Options | 2/3 | 4 logic inputs, 2 isolated outputs, 4 relays, real-time clock data logging, RS232 (DB9) and Ethernet/RF communication ports (not yet available) | ||||||
| Relay Type | 1 | Electromechanical relays only | ||||||
| Relay Type | 2 | 2 electromechanical and 2 solid state relays | ||||||
| Relay Type | 3 | Solid state relays only (not yet available) | ||||||
| Power Supply | E | For 220/240 VAC | ||||||
| Power Supply | A | For 110/120 VAC | ||||||
| Power Supply | D | For DC power only 12-28 VDC | ||||||
| Display Panel Options | F | Fully optioned (with backlight, LCD backup and Infra-Red comms port) | ||||||
| PCB Protection | C | Conformal coating - required for maximum environmental operating range. Recommended to avoid damage from moisture and corrosion. | ||||||
| PCB Protection | N | None - suitable for IEC standard 654-1 Climatic Conditions up to Class B2 (Heated and/or cooled enclosed locations) | ||||||
| Application Pack Number | BF02 | Defines the application software to be loaded into the instrument | ||||||
| Main Menu Variables | Default Units | Preferred Units | Variable Type |
|---|---|---|---|
| Volume | Ltr | Total | |
| Volume Flowrate | L/min | Rate | |
| Control Output | % | Rate | |
| Flowrate Deviation | % | Rate |
Please specify the preferred units of measurement.

500 Series in Ex410 Enclosure
The 515 BF03 application is a batching flow controller for delivery of preset quantities at preset flowrates using a mass frequency input. Batch control can operate in preset or on-off modes, while flow control can be set to local (manual) or PI loop mode.
This application provides the operator with clear local readout including flowrate deviation and can be controlled via communications in more automated systems. There is quick access to commonly used preset values directly from the front panel if access has been authorized.
The PI control of the process flow is via a 4-20mA proportional valve or pump controller. It has integral wind- up protection, a deadband, output hold and ramp time that can be programmed to reduce wear on valves and actuators and provide for bumpless operation.
The total and flowrate are derived from accurately measured frequency and the number of received pulses.
volume = pulses / k-factor
volume flow = frequency / k-factor
Automatic overrun compensation calculates the new valve closure point to ensure correct delivery by averageing the overrun amount from the last three complete batches.
The overrun compensation value is valid for a new preset value provided the stored overrun is less than 20% of the new preset.

The front panel display shows the current values of the input variables and the results of the calculations. A list of the variables for this application and their type (total or rate) is shown at the end of this document.
The instrument can be supplied with a real-time clock for storage of up to 100 transactions with time and date stamps.
There are three communication ports available as follows:
The ports are available for remote data reading, printouts and for initial application loading of the instrument.
The opto-isolated outputs can retransmit any main menu variable. The type of output is determined by the nature of the assigned variable. Totals are output as pulses and rates are output as 4-20 mA signals. One output is standard, a second output is available as an option.
The relay outputs 1 and 2 are used to control the flow of product for each delivery. These contacts are normally open and can be used to drive external relays, valves, pump circuits etc.
The instrument can be further tailored to suit specific application needs including units of measurement, custom tags, second language or access levels. A distributor can configure these requirements before delivery.
Instrument parameters including units of measurement can be programmed in the field, according to the user access levels assigned to parameters by the distributor.
All set-up parameters, totals and logged data are stored in non-volatile memory with at least 30 years retention.

| Terminal Label | Designation | Comment | ||
|---|---|---|---|---|
| 1 | FINP | 1+ | Frequency Input 1+ | Mass flow Input |
| 3 | SG | - | Signal Ground | |
| 15 | Vo | + | 8-24 volts DC output | Overload protected |
| 16 | G | - | DC Ground | |
| 17 | Vi | + | DC power input | DC power in 12-28V |
| 18 | SH | E | Shield terminal | |
| 19 | RS485 | + | RS485 (+) | Advanced option |
| 20 | RS485 | - | RS485 (-) | Advanced option |
| 21 | RS485 | G | RS485 Ground | Advanced option |
| 22 | LOGIC INPUTS | 1+ | Switch 1 | Remote Run |
| 23 | LOGIC INPUTS | 2+ | Switch 2 | Remote Stop |
| 24 | LOGIC INPUTS | 3+ | Switch 3 | Remote Reset |
| 25 | LOGIC INPUTS | 4+ | Switch 4 | Permissive Input |
| 26 | LOGIC INPUTS | C- | Signal ground | |
| 27 | OUT 1 | + | Output ch 1 (+) | Process control output |
| 28 | OUT 1 | - | Output ch 1 (-) | Process control output |
| 29 | OUT 2 | + | Output ch 2 (+) | Optional Output |
| 30 | OUT 2 | - | Output ch 2 (-) | Optional Ouput |
| 31 | RELAYS | RC | Relay common | |
| 32 | RELAYS | R1 | Relay 1 | Single stage control |
| 33 | RELAYS | R2 | Relay 2 | Dual stage control |
| 34 | RELAYS | R3 | Relay 3 | Advanced option |
| 35 | RELAYS | R4 | Relay 4 | Advanced option |
| E | AC MAINS | E | Mains ground | AC power in 95-135V or 190-260V |
| N | AC MAINS | N | Mains neutral | AC power in 95-135V or 190-260V |
| A | AC MAINS | A | Mains active | AC power in 95-135V or 190-260V |
| RS232 port | 9-pin serial port |
515.XXXXXX-BF03
See product codes to select required features
Default application software:
515-BF03-000000

Operating Environment
-20 °C to +60 °C (conformal coating)
+5 °C to +40 °C (no coating)
0 to 95% non condensing (conformal coating)
5% to 85% non condensing (no coating)
95…135 V AC or 190…260 V AC or
12…28 V DC
6W (typical)
Sealed to IP65 (Nema 4X) when panel mounted
147 mm (5.8″) width
74 mm (2.9″) height
167 mm (6.6″) depth
Display
Backlit LCD with 7-digit numeric display and 11-character alphanumeric display
15.5 mm (0.6″) high
6 mm (0.24″) high
Last data visible for 15 min after power down
0.3 second
Non-volatile Memory
> 30 years
Setup, Totals and Logs
Approvals
CE compliance
ATEX, FM, CSA and SAA approved enclosures available for hazardous areas
Real Time Clock (Optional)
3 volts Lithium button cell (CR2032)
5 years (typical)
Frequency Input (General)
0 to 10 kHz
30 V maximum
0.3 sec
Programmable
Pulse, coil or NPS input
Up to 10 correction points
Pulse
CMOS, TTL, open collector, reed switch
1.3 volts
Coil
Turbine and sine wave
15 mV p-p minimum
NPS
NPS sensor to Namur standard
Logic Inputs
CMOS, TTL, open collector, reed switch
30V maximum
Relay Output
2 relays plus 2 optional relays
250 volts AC, 30 volts DC maximum (solid state relays use AC only)
3 A maximum
Communication Ports
RS-232 port
RS-485 port (optional)
Infra-red port
2400 to 19200 baud
Odd, even or none
1 or 2
ASCII, Modbus RTU, Printer
Transducer Supply
8 to 24 volts DC, programmable
70 mA @ 24 V, 120 mA @ 12 V maximum
Power limited output
Isolated Output
1 configurable output (plus 1 optional)
Pulse/Digital or 4-20 mA output
Pulse/Digital Output
Open collector
200 mA, 30 volts DC maximum
0.8 volts maximum
Programmable: 10 , 20, 50, 100, 200 or 500ms
4-20mA Output (Optional)
9 to 30 volts DC external
0.05% full scale
0.05% full scale (20°C)
0.1% (full temperature range, typical)
Important: Specifications are subject to change without notice.
| Model | Supplementary Code | Description | ||||||
|---|---|---|---|---|---|---|---|---|
| 515 | - | BF03 | ||||||
| Enclosure | 1 | Panel mount enclosure | ||||||
| Enclosure | 2 | Field mount enclosure (not yet available) | ||||||
| Enclosure | 3/5 | Explosion proof Ex410 with metric glands (5 specifies heater version) | ||||||
| Enclosure | 4/6 | Explosion proof Ex410 with NPT glands (6 specifies heater version) | ||||||
| Output Options | 0 | 4 logic inputs, 1 isolated output, 2 relays (only relay type 1 is available), RS232 (DB9) communication port | ||||||
| Output Options | 1 | 4 logic inputs, 2 isolated outputs, 4 relays, real-time clock data logging, RS232 (DB9) and RS485 communication ports | ||||||
| Output Options | 2/3 | 4 logic inputs, 2 isolated outputs, 4 relays, real-time clock data logging, RS232 (DB9) and Ethernet/RF communication ports (not yet available) | ||||||
| Relay Type | 1 | Electromechanical relays only | ||||||
| Relay Type | 2 | 2 electromechanical and 2 solid state relays | ||||||
| Relay Type | 3 | Solid state relays only (not yet available) | ||||||
| Power Supply | E | For 220/240 VAC | ||||||
| Power Supply | A | For 110/120 VAC | ||||||
| Power Supply | D | For DC power only 12-28 VDC | ||||||
| Display Panel Options | F | Fully optioned (with backlight, LCD backup and Infra-Red comms port) | ||||||
| PCB Protection | C | Conformal coating - required for maximum environmental operating range. Recommended to avoid damage from moisture and corrosion. | ||||||
| PCB Protection | N | None - suitable for IEC standard 654-1 Climatic Conditions up to Class B2 (Heated and/or cooled enclosed locations) | ||||||
| Application Pack Number | BF03 | Defines the application software to be loaded into the instrument | ||||||
| Main Menu Variables | Default Units | Preferred Units | Variable Type |
|---|---|---|---|
| Mass | kg | Total | |
| Mass Flowrate | kg/min | Rate | |
| Control Output | % | Rate | |
| Flowrate Deviation | % | Rate |
Please specify the preferred units of measurement.

500 Series in Ex410 Enclosure
The 515 BF04 application is a batching flow controller for delivery of preset quantities at preset flowrates using a mass analog input. Batch control can operate in preset or on-off modes, while flow control can be set to local (manual) or PI loop mode.
This application provides the operator with clear local readout including flowrate deviation and can be controlled via communications in more automated systems. There is quick access to commonly used preset values directly from the front panel if access has been authorized.
The PI control of the process flow is via a 4-20mA proportional valve or pump controller. It has integral wind- up protection, a deadband, output hold and ramp time that can be programmed to reduce wear on valves and actuators and provide for bumpless operation.
To derive the flow rate, the analog input is normalised to a value (A) between 0 and 1.
mass flow = (Mf max – Mf min)A + Mf min mass = ∫( massflow × Δt )
Automatic overrun compensation calculates the new valve closure point to ensure correct delivery by averageing the overrun amount from the last three complete batches.
The overrun compensation value is valid for a new preset value provided the stored overrun is less than 20% of the new preset.

The front panel display shows the current values of the input variables and the results of the calculations. A list of the variables for this application and their type (total or rate) is shown at the end of this document.
The instrument can be supplied with a real-time clock for storage of up to 100 transactions with time and date stamps.
There are three communication ports available as follows:
The ports are available for remote data reading, printouts and for initial application loading of the instrument.
The opto-isolated outputs can retransmit any main menu variable. The type of output is determined by the nature of the assigned variable. Totals are output as pulses and rates are output as 4-20 mA signals. One output is standard, a second output is available as an option.
The relay outputs 1 and 2 are used to control the flow of product for each delivery. These contacts are normally open and can be used to drive external relays, valves, pump circuits etc.
The instrument can be further tailored to suit specific application needs including units of measurement, custom tags, second language or access levels. A distributor can configure these requirements before delivery.
Instrument parameters including units of measurement can be programmed in the field, according to the user access levels assigned to parameters by the distributor.
All set-up parameters, totals and logged data are stored in non-volatile memory with at least 30 years retention.

| Terminal Label | Designation | Comment | ||
|---|---|---|---|---|
| 3 | SG | - | Signal ground | |
| 11 | AINP3 | + | Analog input ch 3 (+) | Main or low flow input |
| 12 | AINP3 | - | Analog input ch 3 (-) | Main or low flow input |
| 13 | AINP4 | + | Analog input ch 4 (+) | High flow stacked input |
| 14 | AINP4 | - | Analog input ch 4 (-) | High flow stacked input |
| 15 | Vo | + | 8-24 volts DC output | Overload protected |
| 16 | G | - | DC Ground | |
| 17 | Vi | + | DC power input | DC power in 12-28V |
| 18 | SH | E | Shield Terminal | |
| 19 | RS485 | + | RS485(+) | Advanced option |
| 20 | RS485 | - | RS485(+) | Advanced option |
| 21 | RS485 | G | RS485 ground | Advanced option |
| 22 | Logic Inputs | 1+ | Switch 1 | Remote Run |
| 23 | Logic Inputs | 2+ | Switch 2 | Remote Stop |
| 24 | Logic Inputs | 3+ | Switch 3 | Remote reset |
| 25 | Logic Inputs | 4+ | Switch 4 | Permissive Input |
| 26 | Logic Inputs | C- | Signal ground | |
| 27 | Out 1 | + | Output ch 1 (+) | Process control output |
| 28 | Out 1 | - | Output ch 1 (-) | Process control output |
| 29 | Out 2 | + | Output ch 2 (+) | Advanced Option |
| 30 | Out 2 | - | Output ch 2 (-) | Advanced Option |
| 31 | RELAYS | RC | Relay Common | |
| 32 | RELAYS | R1 | Relay 1 | Single Stage Control |
| 33 | RELAYS | R2 | Relay 2 | Dual Stage Control |
| 34 | RELAYS | R3 | Relay 3 | Advanced Option |
| 35 | RELAYS | R4 | Relay 4 | Advanced Option |
| E | AC MAINS | E | Mains ground | AC power in 95-135 V or 190-260 V |
| N | AC MAINS | N | Mains neutral | AC power in 95-135 V or 190-260 V |
| A | AC MAINS | A | Mains active | AC power in 95-135 V or 190-260 V |
| RS232 port | 9-pin serial port | |||
515.XXXXXX-BF04
See product codes to select required features
Default application software:
515-BF04-000000

Operating Environment
-20 °C to +60 °C (conformal coating)
+5 °C to +40 °C (no coating)
0 to 95% non condensing (conformal coating)
5% to 85% non condensing (no coating)
95…135 V AC or 190…260 V AC or
12…28 V DC
6W (typical)
Sealed to IP65 (Nema 4X) when panel mounted
147 mm (5.8″) width
74 mm (2.9″) height
167 mm (6.6″) depth
Display
Backlit LCD with 7-digit numeric display and 11-character alphanumeric display
15.5 mm (0.6″) high
6 mm (0.24″) high
Last data visible for 15 min after power down
0.3 second
Non-volatile Memory
> 30 years
Setup, Totals and Logs
Approvals
CE compliance
ATEX, FM, CSA and SAA approved enclosures available for hazardous areas
Real Time Clock (Optional)
3 volts Lithium button cell (CR2032)
5 years (typical)
Analog Input (General)
100 mA absolute maximum rating
< 1.0 sec
4-20 mA, 0-5V and 1-5V input
Up to 20 correction points (flow inputs)
4-20 mA Input
100 ohms (to common signal ground)
0.05% full scale (20 °C)
0.1% (full temperature range, typical)
0-5 or 1-5 Volts Input
10 Mohms (to common signal ground)
0.05% full scale (20 °C)
0.1% (full temperature range, typical)
Logic Inputs
CMOS, TTL, open collector, reed switch
30V maximum
Relay Output
2 relays plus 2 optional relays
250 volts AC, 30 volts DC maximum (solid state relays use AC only)
3 A maximum
Communication Ports
RS-232 port
RS-485 port (optional)
Infra-red port
2400 to 19200 baud
Odd, even or none
1 or 2
ASCII, Modbus RTU, Printer
Transducer Supply
8 to 24 volts DC, programmable
70 mA @ 24 V, 120 mA @ 12 V maximum
Power limited output
Isolated Output
1 configurable output (plus 1 optional)
Pulse/Digital or 4-20 mA output
Pulse/Digital Output
Open collector
200 mA, 30 volts DC maximum
0.8 volts maximum
Programmable: 10 , 20, 50, 100, 200 or 500ms
4-20mA Output (Optional)
9 to 30 volts DC external
0.05% full scale
0.05% full scale (20°C)
0.1% (full temperature range, typical)
Important: Specifications are subject to change without notice.
| Model | Supplementary Code | Description | ||||||
|---|---|---|---|---|---|---|---|---|
| 515 | - | BF04 | ||||||
| Enclosure | 1 | Panel mount enclosure | ||||||
| Enclosure | 2 | Field mount enclosure (not yet available) | ||||||
| Enclosure | 3/5 | Explosion proof Ex410 with metric glands (5 specifies heater version) | ||||||
| Enclosure | 4/6 | Explosion proof Ex410 with NPT glands (6 specifies heater version) | ||||||
| Output Options | 0 | 4 logic inputs, 1 isolated output, 2 relays (only relay type 1 is available), RS232 (DB9) communication port | ||||||
| Output Options | 1 | 4 logic inputs, 2 isolated outputs, 4 relays, real-time clock data logging, RS232 (DB9) and RS485 communication ports | ||||||
| Output Options | 2/3 | 4 logic inputs, 2 isolated outputs, 4 relays, real-time clock data logging, RS232 (DB9) and Ethernet/RF communication ports (not yet available) | ||||||
| Relay Type | 1 | Electromechanical relays only | ||||||
| Relay Type | 2 | 2 electromechanical and 2 solid state relays | ||||||
| Relay Type | 3 | Solid state relays only (not yet available) | ||||||
| Power Supply | E | For 220/240 VAC | ||||||
| Power Supply | A | For 110/120 VAC | ||||||
| Power Supply | D | For DC power only 12-28 VDC | ||||||
| Display Panel Options | F | Fully optioned (with backlight, LCD backup and Infra-Red comms port) | ||||||
| PCB Protection | C | Conformal coating - required for maximum environmental operating range. Recommended to avoid damage from moisture and corrosion. | ||||||
| PCB Protection | N | None - suitable for IEC standard 654-1 Climatic Conditions up to Class B2 (Heated and/or cooled enclosed locations) | ||||||
| Application Pack Number | BF04 | Defines the application software to be loaded into the instrument | ||||||
| Main Menu Variables | Default Units | Preferred Units | Variable Type |
|---|---|---|---|
| Mass | kg | Total | |
| Mass Flowrate | kg/min | Rate | |
| Control Output | % | Rate | |
| Flowrate Deviation | % | Rate |
Please specify the preferred units of measurement.

500 Series in Ex410 Enclosure
The 202A Loop Powered Rate Totaliser is designed to operate with any flowmeter which produces a 4-20mA output, including differential pressure devices, magnetic or vortex flowmeters. The 202A is powered entirely from the 4-20mA current loop and has a maximum of 2.5 volts drop across the input.
The Rate Totaliser is fully programmable with linear or square law input relationships, programmable span, cutoffs and conversion factors. A non-volatile memory stores all set up parameters and totals without the need for internal batteries or external power.
High and low alarms are standard via optically isolated solid state relay outputs. Alternatively, the high alarm output can be programmed to provide a scaled pulse output proportional to the total.
The 202A Rate Totaliser is housed in a rugged, yet attractive, IP67 (Nema 4X) polycarbonate enclosure which is completely watertight. A wall mounting bracket is supplied as standard, while a 2″ pipe mounting bracket is available as an option. Alternatively, the Model 202A can be supplied as a panel mount instrument.
The Model 202A is certified as intrinsically safe to European CENELEC standards, and CSA standards for both the USA and Canada.
Display
LCD which is continuously powered.
Resettable Total
7 digits with 10mm (0.4″) high digits. Resettable from front panel.
Accumulated Total
Displayed when the Accumulated Total button is pressed.
Rate
4 digits with 8.5mm (0.33″) high digits.
Span
The units of measure per timebase (eg. gallons/sec) is programmable up to 999,999.
Decimal Points
Decimal point positions are fully programmable for both rate and total.
Timebase
Span can be programmed in units per second, minute, hour or day.
Signal Type
4-20mA.
Temperature
Operating temperature: -20°C to 60°C.
Dimensions
98mm (3.9″) high x 152mm (6.0″) wide x 43mm (1.7″) deep (cable glands not included).
Protection
Sealed to Nema 4X or IP67 standards.
Cable Entry
By cable glands.
Wall Mounting
Universal mounting bracket supplied as standard.
Pipe Mounting
A galvanised metal bracket is available which enables the Model 202A to be attached to a 2″ vertical or horizontal pipe.
Panel Mounting
Supplied with mounting brackets. Terminals accessible from rear. (Note that the panel mount version is not watertight.)
Resolution & Linearity
0.05% of span.
Accuracy
0.05% of span @ 25°C. 0.1% (typ) of span, full temperature range.
Update Time
0.5 seconds.
Connection
Two wire.
Voltage Drop
2.5 volts maximum.

Type
Two solid state relay outputs suitable
for driving DC solenoids or external
relays. The outputs provide high and
low flow alarms; or pulse output and low
flow alarm.
Switching Power
200mA. 30VDC maximum.
Saturation Voltage
0.8VDC typical across the output in the
“on” state.
Isolation
Both outputs are separately optoisolated.
Pulse Duration
a. 1ms if output frequency > 50Hz,
b. 10ms if output frequency is 5…50Hz,
c. 100ms if output frequency is < 5Hz
CENELEC Approval
Type Ex ia IIB T4
CSAUS/C Approval
Type Class 1, Groups C & D
4-20mmA Input
Ui = 28V maximum
Ii = 93mA maximum
Pi = 653mW maximum
Relay/Pulse Outputs
Ui = 28V
Ii = 93mA
Pi = 653mW maximum
Common all models Number 3 4-20mA (-) Input 4 4-20mA (+) Input 5 Low Alarm (-) 6 Low Alarm (+) 7 High Alarm (-) or Pulse (-) 8 High Alarm (+) or Pulse (+)

When specifying please indicate model(s) required using the following method.