Overview
The 505 BC01 application is a dual stage batch controller for reliable measurement of preset quantities using a volumetric frequency input. Used as a single or dual stage contoller it is suitable for fast batch applications.
It provides the operator with clear local readout and can be controlled via communications in more automated systems. There is quick access to commonly used preset values directly from the front panel if access has been authorized. Automatic overrun compensation caters for system delays such as valve closure for precise volumes.
The instrument is compatible with a wide range of flowmeter frequency outputs, including millivolt signals, reed switches, Namur proximity switches and pulse trains via its smart front-panel program selection.
Calculations
The total and flowrate are derived from accurately measured frequency and the number of received pulses.
volume = pulses / k-factor
volume flow = frequency / k-factor
Automatic overrun compensation calculates the new valve closure point to ensure correct delivery by averaging the overrun amount from the last three complete batches.
The overrun compensation value is valid for a new preset value provided the stored overrun is less than 20% of the new preset.
Features at a glance
- Tailored for volumetric frequency flow input
- Single or Dual stage control
- Quick access to common batch quantities
- No-flow, leakage and overflow error detection
- Remote RUN/STOP/RESET
- Allows for non-linear correction
- Storage of 100 transactions with time and date stamp
- Selection of second language and user tags
- Selectable protocols on serial ports including Modbus RTU and Printer output
- Backlit display with LCD backup

Displayed Information
The front panel display shows the current values of the input variables and the results of the calculations. A list of the variables for this application and their type (total or rate) is shown at the end of this document.
The instrument can be supplied with a real-time clock for storage of up to 100 transactions with time and date stamps.
Communications
There are three communication ports available as follows:
- RS-232 port
- RS-485 port
- Infra-red port (optional)
The ports are available for remote data reading, printouts and for initial application loading of the instrument.
Retransmission & Control Outputs
The instrument can retransmit any main menu variable.
The digital outputs can retransmit totals as pulses or operate as logic levels for control or error outputs. If the instrument has the advanced option, it outputs rates as a 4-20 mA signal.
Relay Outputs
The relay outputs 1 and 2 are used to control the flow of product for each delivery. These contacts are normally open and can be used to drive external relays, valves, pump circuits etc.
Software Configuration
The instrument can be further tailored to suit specific application needs including units of measurement, custom tags, second language or access levels. A distributor can configure these requirements before delivery.
Instrument parameters including units of measurement can be programmed in the field, according to the user access levels assigned to parameters by the distributor.
All set-up parameters, totals and logged data are stored in non-volatile memory with at least 30 years retention.

Terminal Designations
| Terminal Label | Designation | Comment | ||
|---|---|---|---|---|
| 1 | RS485 | + | RS485(+) | |
| 2 | RS485 | - | RS485(-) | |
| 3 | RS485 | G | Comms ground | |
| 4 | RS232 | Tx | RS232 data Out | Same RS232 port as DB9 connector |
| 5 | RS232 | Rx | RS232 data in | Same RS232 port as DB9 connector |
| 6 | RS232 | C | CTS (Clear to send) | Same RS232 port as DB9 connector |
| 7 | lo | + | 4-20 mA output | Advanced option |
| 8 | SG | - | Signal Ground 0 V | |
| 9 | Li | + | Logic input | Remote Run |
| 10 | D OUT | 1+ | Open collector o/p 1 | Digital outputs |
| 11 | D OUT | 2+ | Open collector o/p 2 | Digital outputs |
| 12 | li | + | Signal input | Remote stop/reset |
| 13 | SG | - | Signal Ground 0 V | |
| 14 | Fi | + | Frequency input | Volumetric flow |
| 15 | V0 | + | 8-24 volts DC output | 70 mA power limited |
| 16 | G | - | DC Ground | |
| 17 | Vi | + | DC power input | DC power in 12-28 V |
| 18 | SH | E | Shield terminal | |
| 19 | RELAYS | R1 | Relay 1 | Single Stage |
| 20 | RELAYS | RC | Relay Common | |
| 21 | RELAYS | R2 | Relay 2 | Dual Stage |
| E | AC MAINS | E | Mains ground | AC power in 95-135 V or 190-260 V |
| N | AC MAINS | N | Mains neutral | AC power in 95-135 V or 190-260 V |
| A | AC MAINS | A | Mains active | AC power in 95-135 V or 190-260 V |
| RS232 port | 9-pin serial port | |||
505 BC01 Dimension Drawings
Part Number
505.XXXXXX-BC01
See product codes to select required features
Default application software:
505-BC01-000000
505 Specifications
Operating Environment
Temperature
0 °C to +60 °C (conformal coating)
+5 °C to +40 °C (no coating)
Humidity
0 to 95% non condensing (conformal coating)
5% to 85% non condensing (no coating)
Power Supply
95…135 V AC or 190…260 V AC or 12…28 V DC
Consumption
6W (typical)
Protection
Sealed to IP65 (Nema 4X) when panel mounted
Dimensions
147 mm (5.8″) width
74 mm (2.9″) height
167 mm (6.6″) depth
Display
Type
LCD with 7-digit numeric display and 11-character alphanumeric display (backlit optional)
Digits
15.5 mm (0.6″) high
Characters
6 mm (0.24″) high
LCD Backup
Last data visible for 15 min after power down (optional)
Update Rate
0.3 second
Non-volatile Memory
Retention
> 30 years
Data Stored
Setup, Totals and Logs
Approvals
Interference
CE compliance
Enclosure
ATEX, FM, CSA and SAA approved enclosures available for hazardous areas
Real Time Clock (Optional)
Battery Type
3 volts Lithium button cell (CR2032)
Battery Life
5 years (typical)
Frequency Input (General)
Range
0 to 10 kHz
Over Voltage
30 V maximum
Update Time
0.3 sec
Cutoff Frequency
Programmable
Configuration
Pulse, coil or NPS input
Non-linearity
Up to 10 correction points
Pulse
Signal Type
CMOS, TTL, open collector, reed switch
Threshold
1.3 volts
Coil
Signal Type
Turbine and sine wave
Sensitivity
15 mV p-p minimum
NPS
Signal Type
NPS sensor to Namur standard
Remote Logic Inputs
Signal Type
Voltage free contact, open collector
Relay Output
No. of Outputs
2 relays
Voltage
250 volts AC, 30 volts DC maximum
Current
3 A maximum
Communication Ports
Ports
RS-232 port
RS-485 port
Infra-red port (optional)
Baud Rate
2400 to 19200 baud
Parity
Odd, even or none
Stop Bits
1 or 2
Data Bits
8
Protocols
Modbus RTU, Printer*
Transducer Supply
Voltage
8 to 24 volts DC, programmable
Current
70 mA @ 24 V, 120 mA @ 12 V maximum
Protection
Power limited output
Pulse/Digital Output
Signal Type
Open collector, non-isolated
Switching
200 mA, 30 volts DC maximum
Saturation
0.8 volts maximum
Pulse Width
Programmable: 10 , 20, 50, 100, 200 or 500ms
4-20mA Output (Optional)
Supply
24 volts DC internal, non-isolated
Resolution
0.05% full scale
Accuracy
0.05% full scale (20°C)
0.1% (full temperature range, typical)
Important: Specifications are subject to change without notice. Printer protocol is available only if RTC option is installed.
Ordering Information
Product Codes
| Model | Supplementary Code | Description | ||||||
|---|---|---|---|---|---|---|---|---|
| 505 | - | BC01 | ||||||
| Enclosure | 1 | Panel mount enclosure | ||||||
| Enclosure | 2 | Field mount enclosure (not yet available) | ||||||
| Enclosure | 3/5 | Explosion proof Ex410 with metric glands (5 specifies heater version) | ||||||
| Enclosure | 4/6 | Explosion proof Ex410 with NPT glands (6 specifies heater version) | ||||||
| Output Options | 0 | Basic - RS232 and RS485 serial ports, 2 relays, 2 pulse outputs, rear key input | ||||||
| Output Options | 1 | Advanced - also includes 4-20mA o/p and Real-time clock for printer output and logging (100 logs) | ||||||
| Extra Options | 2 | 9 way DB connector for RS232 serial port | ||||||
| Power Supply | E | For 220/240 VAC | ||||||
| Power Supply | A | For 110/120 VAC | ||||||
| Power Supply | D | For DC power only 12-28 VDC | ||||||
| Display Panel Options | S | Standard (no backlight, LCD backup or Infra-Red comms port) | ||||||
| Display Panel Options | F | Fully optioned (with backlight, LCD backup and Infra-Red comms port) | ||||||
| PCB Protection | C | Conformal coating - required for maximum environmental operating range. Recommended to avoid damage from moisture and corrosion. | ||||||
| PCB Protection | N | None - suitable for IEC standard 654-1 Climatic Conditions up to Class B2 (Heated and/or cooled enclosed locations) | ||||||
| Application Pack Number | BC01 | Defines the application software to be loaded into the instrument | ||||||
Main Menu Variables
| Main Menu Variables | Default Units | Preferred Units | Variable Type |
|---|---|---|---|
| Volume | L | Total | |
| Volume Flowrate | L/min | Rate |

500 Series in Ex410 Enclosure