Overview
The 430D Batch Controller is suited to applications where precise measurement and control of variable batch quantities is required.
The instrument is extremely flexible and easy to operate. Batches can be started, paused, stopped and reset via four operational keys and batch quantities and calibration parameters are entered via a 12 key numeric keypad.
Batch Total, Flow Rate, Accumulated Total and Preset Value can all be displayed in engineering units on the green LED display.
The 430D will accept most frequency and pulse signals, including mV outputs from turbine flowmeters, and two-wire proximity switch outputs.
Batch Features
Automatic Overrun Compensation Based on previous batches, the 430D will automatically compensate for any overrun which may be caused by slow closing valves.
Features at a glance
- Accepts pulse and frequency flow signals
- Scaled pulse output
- Overrun compensation
- One or two stage valve control
- Optional RS232/422/485 interfaces for computers and printers
- Remote start/stop
- No-signal alarm
- Ticket printing with time and date
- Displays batch total, preset quantity, flow rate and accumulated total
430D Batch Controller
Computer/Printer Interface
An RS232 and RS422/485 option is available for interfacing to computers and printers. The interface allows the Batch Controller to be fully controlled from a computer.
Software drivers are included for a number of printers and can print a ticket with time and date, a sequential delivery/batch number and the batch and accumulated totals. An optional header for the ticket can also be printed.
Rate Totaliser Mode
The 430D can be configured during calibration to operate as a Rate Totaliser as distinct from a batch controller.
In this mode the RUN, STOP and Batch Set keys perform no function. The Rate key is used to toggle the display between Rate and Resettable Total.
By pressing and holding the Accum. key, whenever the instrument is not in data entry mode, the Accumulated Total will be displayed.
Versatile performance options
The instrument will operate from 14 to 28V dc or from 110 to 220V ac mains.
The facia is fully watertight to Nema 4X (IP65) and is resistant to most chemicals.
A total conversion feature enables the rate to be displayed in one engineering unit (eg. gallons/minute) and the totals to be displayed in another engineering unit (eg. barrels).
The standard instrument is supplied as panel mount. Field enclosures are optionally available.
Operation
Keypad operations are straightforward and four LED’s indicate the operational status at all times.
The unique keypad simplifies operation, making the instrument suited to use by operators with minimal training.
Four operational keys and a full numeric keypad on the front facia, enable the batch quantity to be set, and batch operations to be started, paused, stopped or reset.
Setting Batch Quantity
To set a batch quantity, the Batch Set key is pressed, and then the quantity is entered via the numeric keys. Once set, the Batch Set key is again pressed to return to Run mode.
The batch quantity can only be set while the instrument is in a non- operational state such as when the batch is complete or paused.
Once set, the batch quantity will be retained in non-volatile memory and will not alter until changed by the user.
To check the batch quantity while a batch is in progess press the Batch Set key.
Starting a Batch
To start the batch the RUN key is pressed. The Run LED will light and the instrument will begin to totalise from zero or, if programmed for the count down mode, the display will decrement from the batch quantity.
Stopping a Batch
The batch can be stopped at any time by pressing the STOP key. To continue the batch press the RUN key, or to abort the batch press the STOP key again.
When the batch has been interrupted the Pause LED will light. If the batch is aborted the Stop LED will light.
Resetting a Batch
The instrument can be programmed to reset in either of two ways.
By manually pressing the Reset key, at the end of a batch, the Batch Total will be reset to zero (if programmed to count up) or to the preset quantity (if programmed to count down).
If Auto Reset is programmed, however, the Batch Total will automatically reset when the RUN key is pressed.
One or two stage valve control
Two output relays provide control for single or dual stage valve operation. The first relay will energise at the start of the batch, and de-energise when the batch is complete.
The second relay can be programmed to energise at a set time after the start, and to de- energise at a set quantity prior to completion of the batch. This feature enables a slow startup and slow shutdown of the flow.
The Batch Controller can also be programmed to count up from zero or down from the batch quantity.
Specifications
General
Display
6 digit 0.4” (10.2mm) high green LED
Display Update Rate
0.25s
Data Retention
All set-up parameters and totals are stored in a non-volatile memory with 10 years retention
Transducer Supply
8-24V dc field adjustable, 65mA max
Power Requirements
dc Supply:
14 to 28V dc, 300mA typical (no options)
ac Supply:
ac mains set internally to 95-135V ac or 190-260V ac
Operating Temperature
0 to 55°C
Relay Outputs
Maximum Power
1250VA
Maximum Voltage
250V ac, 30V dc
Maximum Current
5 Amps
Pulse Output
Pulse Width
10ms (negative going pulse).
Max Duty Cycle
49 pulses per second
Scaling
The pulse output is scaled and outputs one pulse each time the accumulated total increments
Approvals
Electrical
ETL (US) approved to UL508 and CSA
Interference
CE Compliance
Frequency Input
Frequency Range
Minimum:
0.25Hz on Rate, 0Hz on Total
Maximum:
10KHz
Scaling Range
0.100 to 50,000
Switching Threshold
2.5V (except for Namur proximity and coil input types)
Maximum Input Voltage
50V peak
Input Impedance
Logic Signal, CMOS, Pulse:
100KW
Open Collector or Reed Switch:
10KW
Namur Proximity (set dc out to 8v):
1KW
Switch or Reed Switch with debounce circuit (200Hz max):
10KW
Coil (20mC P-P min):
100KW
Coil (22mV P-P min):
2.4KW
Optional Enclosures
Field Enclosures
IP67 (Nema 4X)
Important: Specifications are subject to change without notice.
Dimensional Drawing

Terminal Descriptions
| RS232/422/485 Options All Models | |
|---|---|
| No. | |
| 20 | RS232 Signal Ground |
| 21 | RS232 Data In |
| 22 | RS232 Data Out |
| 23 | RS422/485 (-) Data Out |
| 24 | RS422/485 (+) Data Out |
| 25 | RS422/485 (-) Data In |
| 26 | RS422/485 (+) Data In |
| 27 | RS232 CTS |
| Relay Outputs & Switches 430D | |
|---|---|
| No. | |
| 28 | Not to be used |
| 29 | Not to be used |
| 30 | End of Batch/Pump Control Signal |
| 31 | Relay 2 - Normally Open |
| 32 | Relay 2 - Normally Closed |
| 33 | Relay 2 - Common |
| 34 | Relay 1 - Normally Open |
| 35 | Relay 1 - Normally Closed |
| 36 | Relay 1 - Common |
| Standard Terminal Connections 430D | |||
|---|---|---|---|
| No. | No. | ||
| 1 | Calibration Link | 8 | Flow Common (-) |
| 2 | Signal Ground | 9 | Flow Pulse Input |
| 3 | Remote RUN Switch | 10 | Pulse Out |
| 4 | Remote Rate Switch | 11 | dc Power Out (8-24V) |
| 5 | Remote Reset Switch | 12 | dc Ground |
| 6 | Remote STOP Switch | 13 | dc Power Input |
| 7 | Flow Alarm | 14 | Not to be used |
Ordering Information