400 Series
Instrumentation with Liquid Temperature Compensation


405L / 414L

Overview

Mass Flow measurement at a comparatively low cost can be achieved using the Model 405L and 414L instruments, an RTD temperature sensor and a volumetric flowmeter such as a turbine or positive displacement meter.

Volume correction to 15°C or 60°F for petroleum products is also possible. Petroleum tables and equations that comply with API/ASTM standards for metric and US units are included in both instruments.

With additional features such as a 10 point non-linearity correction and quadrature pulse input, the Models 405L and 414L are ideally suited to the precise measurement of flow, as required in custody transfer applications.

Displayed Information

The 405L Flow Computer displays Flow Rate, Resettable Total, Accumulated Total, Gross Total and Temperature.

The 414L Batch Controller displays Batch Total, Preset Quantity, Accumulated Total, Flow Rate, Gross Total and Temperature.

Computer/Printer Interface

An RS232/422/485 option enables ticket printing and communications with a computer. Software drivers are included for a number of printers.

A ticket with time and date, a sequential delivery/batch number and the gross, net and accumulated totals can be printed with an optional header if required.

Quadrature input capability

Quadrature applies only to frequency type inputs and requires two input signals, 90° out of phase, from a single flowmeter. Through the phasing of signals, forward and reverse flows can be detected, as well as loss of signal.

This capability makes the 405L and 414L suitable for custody transfer applications where integrity of signal can be assured.

Features at a glance

  • Mass Flow calculation
  • Volume Correction for petroleum products
  • Single and quadrature pulse inputs
  • Ticket printing option with time and date

Applications

  • General liquids
  • Petroleums
  • LPG
  • Custody Transfer
  • Truck Mounted

Versatile performance options

The 414L incorporates two relays that can be used to control a single or two stage control valve.

Both instruments will operate from 12 to 28V dc or from 110/220V ac mains.

The facias are watertight to Nema 4X (IP65) and resistant to most chemicals.

Each instrument is supplied with a sheet of self-adhesive engineering unit labels. A recess, adjacent to the display, is provided in which the correct label can be placed.

The instruments are supplied as standard in a panel mount enclosure. Field enclosures and explosionproof enclosures are optionally available.

Input Options

The input options for the 405L and 414L are shown in the following table:

Model405LA405LR414LA414LR
Temperature
4-20mA
RTD
Frequency
Single
Quadrature
Analog FLow
4-20mA
Density
4-20mA

405 Flow Measurement Computer

Temperature Compensation

Three methods of compensation are built into the instruments with the appropriate method selected during setup.

Density Correction

Providing a fluid has a known relationship between density and temperature, the density can be determined by measuring the temperature. Up to five temperature and density points can be programmed and the resulting curve is used to determine density.

The Mass Flow is then calculated as:

Mass Flow = Volumetric Flow x Density

The volumetric flow can be accurately determined by turbine, positive displacement or vortex flowmeters.

(Note: Non-volumetric inputs from pressure transmitters can also be handled.)

Volume Correction for Petroleums

Volume correction to 15°C or 60°F, as determined by API/ASTM Tables for metric and US units, is possible to the following tables:

Crude Oil: Tables 24A and 54A

Gasoline, Jet Fuels, Kerosene & Solvents: Tables 24B and 54B

Diesel, Heating Oils & Fuel Oils: Tables 24C and 54C

LPG: Tables 34 and 54

Volume Correction for General Liquids

The thermal co-efficient of expansion can be programmed and a volume corrected flow, to a programmable base temperature, will be calculated as follows:

Net Flow =

Volumetric Flow

1 + (Tf – Tb) . a

where

Tf is the flow temperature (°C or °F).

Tb is the base temperature (°C or °F).

a is the thermal co-efficient of expansion.

Batch Control – 414L

One or two stage valve control

Two output relays provide control for single or dual stage valve operation. The first relay will energise at the start of the batch and de-energise when the batch is complete.

The second relay can be programmed to energise at a set time after the start, and to de-energise at a set quantity prior to completion of the batch. This feature enables a slow start-up and slow shutdown of the flow.

The Batch Controller can also be programmed to count up from zero or down from the batch quantity.

405 Flow Measurement Computer diagram

Batch Functions

Batch Total

Batching can be performed on the Gross Total, or on the Net Total (or Mass Total).

Remote Start/Stop

Inputs on rear panel to connect momentary switches to the RUN and STOP keys.

Signal Timeout

If the flow cuts out midway through a batch, the outputs are de-energised and an alarm signalled. Timeout: 0-999s.

Batch Limit

The maximum batch limit can be programmed.

End of Batch

An open collector output signals the end of batch.

Auto-Restart

The Batch Controller can be programmed to continually repeat batches with a delay of up to 99 minutes between batches.

Batch Operations

Four key switches on the front facia, enable the batch quantity to be set, and batch operations to be started, stopped or reset.

To set batch quantity, The Batch Set key is pressed, and then the > and ± keys can be used to change and increment digits. Once set, the Batch Set key is again pressed to return to RUN mode. Key operations are straight forward and four LED’s indicate the operational status at all times.

In the RUN mode, the Display key can be used to display Flow Rate, Gross Total, Accumulated Total and Temperature.

The unique four-key operation of the Batch Controller is designed to simplify operation, making the instrument suited to use by operators with minimal training.

Specifications

General

Display

6 digit 0.7” (17.8mm) high LCD.

Display Update Rate

0.25s.

Data Retention

All set-up parameters and totals are stored in a non-volatile memory with 10 years retention.

Transducer Supply

8-24V dc field adjustable, 50mA maximum.

Power Requirements

dc Supply:

11.5-28.5V dc, 130mA typical current (no options).

ac Supply:

ac mains set internally to 95-135V ac or 190-260V ac.

Operating Temp

0 to 55ºC.

Frequency Input

Frequency Range

Rate:

0.25 to 10kHz.

Total:

0 to 10kHz.

Input Circuits

Will accept most logic, proximity switch, mV, pulse and reed switch inputs.

Scaling Range

0.1000 to 50,000.

RTD Input

Measurement

Range:

-100ºC (212ºF) to 200ºC (392ºF).

Accuracy:

0.1ºC.

RTD Type

PT100.

Linearity Correction

Internally compensated.

Adjustment

Offset can be programmed to compensate for RTD tolerance.

4-20mA Inputs

Measured

Flow, temperature and density.

Input Impedance

250 ohms.

Measurement Accuracy

0.05%.

Isolation

Inputs are non-isolated.

Tempereature Measurement Ranges

General Liquids

-273ºC to 200ºC (-459ºF to 392ºF).

Petroleums

-100ºC to 200ºC (-148ºF to 392ºF).

LPG

-45ºC to 60ºC (-49ºF to 140ºF).

Pulse Output

Type

Open collector.

Pulse Width

10ms (negative going pulse).

Max Rate

49 pulses per second.

Scaling

The pulse output is scaled and outputs one pulse each time the accumulated total increments.

Relay Outputs

Max Power

1250VA.

Max Voltage

250V ac, 30V dc.

Max Current

5 Amps.

4-20mA Output Option
(Model 405L only)

Resolution

10 bits.

Accuracy

Better than 0.1%.

Maximum Load

500 ohms internally powered. 950 ohms if powered from 24V.

Isolation

Output is isolated.

RS232/422 Option

Baud Rate

300-9600.

Parity

None, odd or even.

Word Length

7 or 8 bits.

ID Code

0-999.

Clock

24 hour clock will keep time for a minimum of 72 hours without power to the instrument.

Date

US or European format.

Optional Enclosures

Field Enclosures

IP67 (Nema 4X).

Explosion proof Enclosures

CENELEC, FM, CSA and SAA approved enclosures available for hazardous areas.

Approvals

Electrical

ETL (US) approved to UL 508 and CSA.

Interference

CE Compliance.

Important: Specifications are subject to change without notice.

Contrec 405 Flow Measurement Computer diagram

Terminal Descriptions


Standard Terminal Connections 405LR/414LR
No.No.
1Calibration Link8Flow Common (-)
2Signal Ground9Flow Pulse Input (Ch. 1)
3Flow Pulse Input (Ch. 2)10Pulse Out
4PT100 I (+)11dc Power Out (8-24V)
5PT100 Signal (+)12dc Ground
6PT100 Signal (-)13dc Power Input
7Flow Alarm14PT100 (-)


Standard Terminal Connections 405LA/414LA
No.No.
1Calibration Link8Flow Common (-)
2Signal Ground9Flow Pulse Input (Ch. 1)
3Flow Pulse Input (Ch. 2)10Pulse Out
4Not to be used11dc Power Out (8-24V)
5Temperature Input (4-20mA)12dc Ground
6Not to be used13dc Power Input
7Flow Alarm14Flow Input (4-20mA)


Relay Outputs 405L
No.
31Relay 2 - Normally Open
32Relay 2 - Normally Closed
33Relay 2 - Common
34Relay 1 - Normally Open
35Relay 1 - Normally Closed
36Relay 1 - Common


Relay Outputs & Switches 414L
No.
28Remote RUN Switch
29Remote STOP Switch
30End of Batch
31Relay 2 - Normally Open
32Relay 2 - Normally Closed
33Relay 2 - Common
34Relay 1 - Normally Open
35Relay 1 - Normally Closed
36Relay 1 - Common


RS232/422/485 Options All Models
No.
20RS232 Signal Ground
21RS232 Data In
22RS232 Data Out
23RS422/485 (-) Data Out
24RS422/485 (+) Data Out
25RS422/485 (-) Data In
26RS422/485 (+) Data In
27RS232 CTS


Analog Flow Output (4-20mA) - 405L Only
No.
20Not to be used
210 Volts
220-10 Volts
23-12 Volts
24I (-)
25I (+)
26+15 Volts
27Not to be used

Ordering Information

When specifying indicate model(s) required using the following method.

405L ordering

Product Manual Download